Cable ladder interlocking ends - KLLI60

Side walls: perforated S-profile
Perforated C rungs 15x30
Usable inner height: 44 mm
Rung distance: 250 mm


ETIM: EC000854


Reference Finish
mm

mm

mm

mm
kg
m
Unit
KLLI60.150 SZ 60 150 1 3000 1.968 30 M
KLLI60.200 SZ 60 200 1 3000 2.085 30 M
KLLI60.300 SZ 60 300 1 3000 2.319 30 M
KLLI60.400 SZ 60 400 1 3000 2.553 30 M
KLLI60.450 SZ 60 450 1 3000 2.670 30 M
KLLI60.500 SZ 60 500 1 3000 2.787 30 M
KLLI60.600 SZ 60 600 1 3000 3.021 30 M
KLLI60.750 SZ 60 750 1 3000 3.373 30 M
KLLI60.800 SZ 60 800 1 3000 3.490 30 M
KLLI60.900 SZ 60 900 1 3000 3.724 30 M
ZMKLLI60.150 DF 60 150 1 3000 1.968 30 M
ZMKLLI60.200 DF 60 200 1 3000 2.085 30 M
ZMKLLI60.300 DF 60 300 1 3000 2.319 30 M
ZMKLLI60.400 DF 60 400 1 3000 2.553 30 M
ZMKLLI60.450 DF 60 450 1 3000 2.670 30 M
ZMKLLI60.500 DF 60 500 1 3000 2.787 30 M
ZMKLLI60.600 DF 60 600 1 3000 3.021 30 M
ZMKLLI60.750 DF 60 750 1 3000 3.373 30 M
ZMKLLI60.800 DF 60 800 1 3000 3.490 30 M
ZMKLLI60.900 DF 60 900 1 3000 3.724 30 M
CHARACTERISTICS
- lightweight
- strong
- interlocking
- partition (SLOS35) can be fixed to the cable ladder with a sliding nut (GM6) and pan head bolt (RB6.10)
- no further coupling holes are required if the cable ladder is cut
- use joiners (KLLKP60) and bolts (VM6.10) to join the cut lengths of cable ladder
- no joiners are required to attach accessories such as bends, tees etc.
- rungs are perforated to enable efficient attachment of cables.
TECHNICAL INFORMATION
Side walls are constructed from S profile with a return flange and are continuously perforated.
C-profile rungs are fixed at 250 mm intervals.
Rungs are mechanically attached to the side wall of the cable ladder.
Rungs are alternately placed with openings upwards and downwards.
Legend finish
- SZ = Sendzimir
- DF = Defender

Technical info

Product datasheet

Questions?

For more info, please contact

vergokanexport@atkore.com
+32 55 31 83 35

Load diagram

KLLI60 LOAD DIAGRAM
This diagram illustrates the permissible uniformly distributed horizontal loads applied to multiple supports. They comply with IEC 61537 with connection in the centre of the span and the end span = 0,8x the span.

F = max. admissible load (daN/m)
L = support distance (m)
Max. deflection (m) = L/100